Physical Specifications: 19"W x 13"H x 16"D (48.3 cm x 33cm x 40.1 cm); Weight: 73 lbs (33.1 kg)
Input Power: 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
Measurement Method: IEC 60044-1, IEC 61869, ANSI/IEEE C57.13.1, and ANSI/IEEE C57.12.90
Current Source: 1 – 20A @ 0 – 15 Vac
Current Source Display: Test current and current on-time
Voltage Reading Range: 0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 V
Current Reading Range: 0 – 10A; Accuracy: ±1.0% of reading, ±0.02A
Phase Angle Measurement: 0 – 360 degrees; Accuracy: ± 1.0 degree)
Resistance Reading Range: 100 micro-ohms – 30 ohms; Accuracy: 2% of reading, ± 1 count, ± 10 micro-ohms
Insulation Resistance Reading Range: 2 Mega-ohms – 500 Mega-ohms; Accuracy: 3% of reading, 500 – 1000 Vdc test voltage
Computer Interfaces: One USB port and Bluetooth wireleass interface
External Data Storage: One USB Flash drive interface port (Flash drive not included)
Safety: Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
Environment: Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
Humidity: 90% RH @ 40°C (104°F) non-condensing
Altitude: 2,000 m (6,562 ft) to full safety specifications