Close
You have no items in your shopping cart.

Vanguard EZCT-2000C Current Transformer Test Set

Manufacturer part number: EZCT-2000C
PURCHASE
AvailableQTYPrice
New:   0
+ -
$0.00
Used:   0
+ -
$0.00Configurations
X

Available Configurations

The EZCT-2000C is Vanguard’s third-generation microprocessor-based current transformer test set. The EZCT-2000C’s test leads can be connected to all the CT output terminals, and the complete CT test can be performed automatically without any operator intervention.

Key Features and Functions

  • Performs CT excitation, current-ratio, polarity, and phase angle tests
  • Measures insulation resistance and winding resistance of the CT secondary windings
  • Measures the CT’s load burden
  • Standalone or computer-controlled via USB or Bluetooth wireless interface
  • Physical Specifications: 19"W x 13"H x 16"D (48.3 cm x 33cm x 40.1 cm); Weight: 73 lbs (33.1 kg)

  • Input Power: 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz

  • Measurement Method: IEC 60044-1, IEC 61869, ANSI/IEEE C57.13.1, and ANSI/IEEE C57.12.90

  • Current Source: 1 – 20A @ 0 – 15 Vac

  • Current Source Display: Test current and current on-time

  • Voltage Reading Range: 0 – 2,200 Vac; Accuracy: ±1.0% of reading, ±1 V

  • Current Reading Range: 0 – 10A; Accuracy: ±1.0% of reading, ±0.02A

  • Phase Angle Measurement: 0 – 360 degrees; Accuracy: ± 1.0 degree)

  • Resistance Reading Range: 100 micro-ohms – 30 ohms; Accuracy: 2% of reading, ± 1 count, ± 10 micro-ohms

  • Insulation Resistance Reading Range: 2 Mega-ohms – 500 Mega-ohms; Accuracy: 3% of reading, 500 – 1000 Vdc test voltage

  • Computer Interfaces: One USB port and Bluetooth wireleass interface

  • External Data Storage: One USB Flash drive interface port (Flash drive not included)

  • Safety: Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards

  • Environment: Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)

  • Humidity: 90% RH @ 40°C (104°F) non-condensing

  • Altitude: 2,000 m (6,562 ft) to full safety specifications

Description

The EZCT-2000C is Vanguard’s third-generation microprocessor-based current transformer test set. The EZCT-2000C’s test leads can be connected to all the CT output terminals, and the complete CT test can be performed automatically without any operator intervention.

Key Features and Functions

  • Performs CT excitation, current-ratio, polarity, and phase angle tests
  • Measures insulation resistance and winding resistance of the CT secondary windings
  • Measures the CT’s load burden
  • Standalone or computer-controlled via USB or Bluetooth wireless interface