Physical Specifications:
- Dimensions: 21K”W x 8”H x 14” D (53 cm x 20 cm x 35 cm)
- Weight: 15 lbs. (6.8 Kg)
Input Power:3A, 100 - 240 VAC, 50/60 Hz
Dry-Contact Inputs:3 channels (9021-UC) or 6 channels (9100-UC). Each channel can detect the main contact and resistor contact time.
Timing Windows: 1 second, 10 seconds, or 20 seconds
Timing Resolutions: ±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milliseconds @ 20 sec. duration
Timing Accuracy: 0.05% of reading ±0.05 milli-seconds @ 1 second duration
Dry-Contact Detection Range: Closed: less than 20 ohms; Open: greater than 5,000 ohms
Resistor Detection Range: 50 - 5,000ohms
Trigger Input Voltage: Open/Close: 24 - 300 V, dc or peak ac
Dry Contact Input Protection: All contact inputs are grounded until test. Input channels are also protected against static discharge.
Breaker Operations: Initiate open, close, open-close, close-open, open-close-open
Voltage Sensing Input Range: V1: analog input; 0 ¬ 250 V dc or peak ac; sensitivity ±1 V; record and print voltage level V2 and V3: voltage presence/absence detector input; 24 ¬ 255 V dc or peak ac; record and print 3 timing events
Breaker Initiate Capacity: 30 A, 250 V ac/dc max
Resistor Type Transducer Inputs: 3 channels, 200 ohms ¬ 10 K ohms
Digital Travel Transducer Input: 3 digital travel transducer channels; linear range: 0.0 - 60.0 in (±0.01 in); rotary range: 0 - 360 degrees (±0.36 degrees)
Initiate Current Reading Range: One, non-contact, Hall-effect sensor, 0 - 20 amp range, dc to 5 Khz ac
Contact Travel Point Difference: Measures “slow-close” contact-point distances; results can be printed
Display: 5" back-lit LCD screen (240 x 128 pixels); viewable in bright sunlight and low light levels
Internal Test Record Storage: Stores up to 200 test records and 100 test plans
Printer: Built-in 4K” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
External Data Storage: USB Flash drive interface for external storage of test records and test plans
PC Software: Windows®-based Circuit Breaker Analysis software (VCBA S2) included with purchase price. Software updates available at no additional charge
Computer Interfaces: One USB port, optional Bluetooth interface
Safety: Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
Humidity: 90% RH @ 40°C (104°F) non-condensing
Temperature: Operating: -10°C to +50°C (+15°F to +122°F) Storage: -30°C to +70°C (-22°F to +158°F)
Altitude: 2,000 m (6,562 ft) to full safety specifications
Cables: 20'(6.1 m) contact leads, 30' (9.1 m) contact lead extensions, 20' (6.1 m) control and voltage cables, 25' (7.6 m) digital transducer cable, USB cable, power cord, ground cable