Close
You have no items in your shopping cart.

Megger DELTA4110 Insulation Diagnostic System

Manufacturer part number: DELTA4110
PURCHASE
AvailableQTYPrice
New:   0
+ -
$0.00
Used:   0
+ -
$0.00Configurations
X

Available Configurations

DELTA4000 series is a fully automatic 12 kV insulation power factor/dissipation factor (tan delta) test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters, and rotating machinery.

Two configurations make up the series:

  • DELTA4110 with the external computer (not included) consists of the DELTA4100 control unit and DELTA4010 high-voltage unit

Features:

  • Power factor test set
  • Automatic and manual operation
  • Accurate and repeatable measurement results with high noise suppression
  • Lightweight, rugged two-piece design
  • New built-in intelligent temperature correction (patent pending)
  • New automatic voltage dependence detection (patent pending)
  • High voltage lead: 21 m (70 ft), double shielded 30012H-11
  • Measurement lead, color-coded red, 21 m (70 ft) 25572-1
  • Measurement lead, color-coded blue, 21 m (70 ft) 25572-2
  • Ground lead: 9 m (30 ft) 2002-131
  • Input power cable 16A EU 17032-29
  • Input power cable 16A US 17032-28
  • Input power cable 16A UK 17032-30
  • Safety hand switch, Interlock #1, 21 m (70 ft) 1001-850
  • Safety foot interlock, 3m (10 ft) 1001-852
  • HV unit power cable, 1 m (3 ft) 2002-132
  • HV unit control cable, 1 m (3 ft) 2002-133
  • Ground lead interconnect cable, 1 m (3 ft) 2002-134
  • USB cable, 2 m (7 ft) CA-USB
  • Ethernet cable, CAT 5, 2 m (7 ft) 36798
  • Backpack lead bag 2012-180
  • Software DELTA manual control 1001-981
  • PowerDB Lite software

Input Power

  • 90 - 264 V 45 - 66 Hz
  • 16 A max
  • No loss in performance when used with portable generator

Output Voltage

  • 0 to 12 kV, continuously adjustable

Test Frequency Range

  • 45-70 Hz (12 kV)
  • 15-400 Hz (4 kV)
  • 1-505 Hz (250V)
  • 0.0001 Hz maximum resolution

Output Power

  • 3.6 kVA

Output Current

  • 300 mA (4 minutes)
  • 200 mA (30 minutes)
  • 100 mA (continuous)
  • The power supply capacity can be expanded to 4 A at 12 kV using the
  • optional Resonating Inductor, (Cat. No. 670600-1)

Measuring Ranges

  • Voltage: 25 V to 12 kV, 1 V resolution
  • Current: 0 to 5 Amps, 0.1 μA maximum resolution. The measurement can be corrected to either 2.5 kV or 10 kV equivalents.
  • Capacitance: 0 to 100 μF, 0.01 pF maximum resolution
  • Inductance: 6 H to 10 MH, 0.1 mH maximum resolution
  • Power factor: 0-100% (0-1), 0.001% maximum resolution
  • Dissipation factor: 0-100 (0-10,000%), 0.001% maximum resolution
  • Watt Loss: 0 to 2 kW, actual power, 0 to 100 kW when corrected to 10 kV equivalent. 0.1 mW maximum resolution. The measurement can be corrected to either 2.5 kV or 10 kV equivalents.
Description

DELTA4000 series is a fully automatic 12 kV insulation power factor/dissipation factor (tan delta) test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters, and rotating machinery.

Two configurations make up the series:

  • DELTA4110 with the external computer (not included) consists of the DELTA4100 control unit and DELTA4010 high-voltage unit

Features:

  • Power factor test set
  • Automatic and manual operation
  • Accurate and repeatable measurement results with high noise suppression
  • Lightweight, rugged two-piece design
  • New built-in intelligent temperature correction (patent pending)
  • New automatic voltage dependence detection (patent pending)